Service 25 / 27 · Cleanroom Classification & Pressure Cascade

Air Should Always Know Which Way to Go.

A pressure cascade that exists only in the HVAC model is difficult to operate and harder to demonstrate. ALVEDA defines the classification of each room, its neighbors and the intended direction of air movement between them, then resolves where airlocks and pass boxes are needed and where containment requires negative pressure instead of product protection. The cascade is documented on a single diagram that architecture, HVAC, controls and the client quality team can all work from, together with a monitoring strategy that shows it is being maintained.

Engineering phases

Where this service fits

05 / 09 phases in scope

  1. 01Feasibilitynot in scope
  2. 02ConceptIn scope
  3. 03Basic EngineeringIn scope
  4. 04Detailed EngineeringIn scope
  5. 05Procurementnot in scope
  6. 06Constructionnot in scope
  7. 07CommissioningIn scope
  8. 08ValidationIn scope
  9. 09Operationnot in scope

Scope

What the service covers

  1. 01Cleanroom zoning and room classification
  2. 02Room adjacency and relative pressure relationships
  3. 03Airlock and pass-box concepts
  4. 04Positive and negative pressure containment strategy
  5. 05Door, envelope and transfer-air considerations
  6. 06Pressure monitoring and alarm strategy

Method

From inputs to deliverables

INInputs

05 items
  1. I01Zoning and flow study or concept layout
  2. I02Room functions and required classifications
  3. I03Hazard classification of materials handled, as defined by the client
  4. I04Process equipment and primary containment devices
  5. I05Quality requirements defined by the client

WORKActivities

06 items
  1. W01Room classification and adjacency review
  2. W02Risk-based definition of pressure relationships
  3. W03Airlock regime selection: cascade, bubble or sink
  4. W04Containment versus product-protection decisions
  5. W05Coordination of the cascade with HVAC airflows and door arrangements
  6. W06Definition of monitoring points and alarm logic

OUTDeliverables

05 items
  1. D-25.01Classification zoning layout
  2. D-25.02Pressure cascade diagram
  3. D-25.03Room adjacency and pressure relationship schedule
  4. D-25.04Airlock and pass-box concept
  5. D-25.05Pressure monitoring and alarm philosophy

Technical detail

How the cascade is defined

  • The cascade starts from which rooms touch which, and what each one must protect.

    • Classification assigned per room
    • Adjacency matrix between rooms and corridors
    • Boundaries between classified and unclassified areas
    • Critical zones and their surrounding background rooms

Illustrative Engineering Model

ALVEDA Facility Intelligence

One compact, generic facility read nine ways — classification, pressure, air handling, the flows of people, materials and waste, utilities, laboratories and containment. Choose a layer, then a room, to see the engineering intent behind it.

Illustrative engineering model of a compact pharmaceutical facility — Classification layer shownALV-FIM-01 · GENERIC COMPACT FACILITY · N.T.S.ILLUSTRATIVE ENGINEERING MODEL — NOT A PROJECT DRAWINGLAYER Z-CLAS

Swipe to see the whole plan · tap a room for details

Illustrative Engineering ModelA generic layout created for explanation, not a project drawing. Classifications, pressure steps and zones are indicative; each project defines its own in the URS and basis of design. Relative relationships only — differential values are set per project.

01 / 09 — Z-CLAS

Classification

Cleanliness classes step up toward the point of exposure. The critical ISO 5 zones exist only inside the PEC and C-PEC, not across whole rooms.

  • ISO 5 — inside PEC / C-PEC
  • ISO 7 — buffer and HD rooms
  • ISO 8 — ante, airlock, production
  • CNC — controlled, not classified
  • Unclassified

Showing layer: Classification

Interactive engineering model

Explore how the engineering fits together.

PC-S

Sterile compounding cascade

Pressure rises toward the critical zone, so air always moves from clean to less clean.

Illustrative Engineering Model
ALV-PC · RELATIVE PRESSURE CASCADE · N.T.S.CORR0CNCANTE++ISO 8BUF+++ISO 7PECUDFISO 5RELATIVE P — STEPS ONLY, NO VALUES0 = CORR

++Ante room

Room function
Hand hygiene, garbing and staging — the buffer between uncontrolled and critical air.
Classification
ISO 8
Relative pressure relationship
Positive to the corridor, negative to the buffer room.
Airflow direction
Air enters from the buffer room and leaves toward the corridor.
Adjacent spaces
Corridor, Buffer room
Design consideration
Mark a line of demarcation between the dirty and clean sides; size the room for peak shift change.

Selected zone: Ante room

Relative relationships only — differential values are set per project.

PC-H

Hazardous drug containment cascade

A positive ante room shields the corridor, while the preparation room is held negative so hazardous particles stay in.

Illustrative Engineering Model
ALV-PC · RELATIVE PRESSURE CASCADE · N.T.S.CORR0CNCHD-A+ISO 7HD-B–ISO 7C-PEC––ISO 5EXH · HEPARELATIVE P — STEPS ONLY, NO VALUES0 = CORR

–HD buffer room

Room function
Houses the containment primary engineering control (C-PEC) used to prepare hazardous drugs.
Classification
ISO 7
Relative pressure relationship
Negative to the HD ante room — the lowest room pressure in the chain.
Airflow direction
Air enters from the ante room and is exhausted to outside, not recirculated to other areas.
Adjacent spaces
HD ante room, C-PEC
Design consideration
Externally vented, sealed room envelope; monitor the negative step continuously with a local display and alarm.

Selected zone: HD buffer room

Relative relationships only — differential values are set per project.

Deliverables

Typical documents and outputs

  1. D-25.01Classification zoning layout
  2. D-25.02Pressure cascade diagram
  3. D-25.03Room adjacency and pressure relationship schedule
  4. D-25.04Airlock and pass-box concept
  5. D-25.05Pressure monitoring and alarm philosophy

Services

Related services

  • 05

    HVAC Engineering

    Air systems designed for cleanliness, pressure, temperature and humidity control.

  • 04

    Cleanroom Design

    Classified spaces with defined pressure cascades, airlocks and gowning sequences.

  • 21

    Hazardous Drug Facility Engineering

    Receiving, storage, compounding, decontamination and waste routes engineered for containment.

Next step

Planning a pharmaceutical project?

Share the product type, the current stage and the main constraints. We will respond with a proposed scope and next steps.